Micro Master 440 fault F0022 repair

From Repair Wiki
Revision as of 11:35, 18 July 2024 by ASRepairs (talk | contribs) (Created page with "{{stub}} {{Repair Guide |Device= |Affects parts= |Needs equipment= |Type= |Difficulty= }} ==Problem description== <!-- Provide a concise description of the issue here. Be as specific as possible to help readers quickly determine whether or not this is the exact problem they are facing. --> Repairing one of the causes for fault code F0022 "Power stack fault" on Siemens micromaster 440 inverter. This solution concerns the main power relay (figure 1) File:20240718 132...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

This article is a stub. You can help Repair Wiki grow by expanding it

Micro Master 440 fault F0022 repair
Device
Affects part(s)
Needs equipment
Difficulty
Type


Problem description

Repairing one of the causes for fault code F0022 "Power stack fault" on Siemens micromaster 440 inverter. This solution concerns the main power relay (figure 1)

Main power relay (Figure 1)

Symptoms

  • Works until a certain frequency/power then shows error F0022
  • General fault F0022 even before starting the motor
  • Shows fault F0022 as soon as starting the motor

Solution

  • First confirm that the main IGBT module is not damaged in any way.
  • Measure each individual IGBT as described here.
  • If the IGBT module is okay, look under the main power relay.
  • In my case, one of the legs was not soldered properly and it was black from overheating.
  • Take out the relay and confirm that it's working by injecting voltage on it's coil and measuring the contacts.
  • If the relay is working properly, repair the hole for the leg or run a thick wire jumper to where it's supposed to go (the wire on the side going to the adjacent PCB, measure with continuity to confirm which exact one).
  • After this the inverter should work properly