Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Simatic PS 307 Not turning on at all repair: Difference between revisions

From Repair Wiki
No edit summary
No edit summary
 
Line 1: Line 1:
{{Repair Guide
{{Repair Guide
|Device=
|Device=Simatic PS 307
|Affects parts=
|Affects parts=TVS 1.5KE200CA, fuse
|Needs equipment=
|Needs equipment=multimeter, soldering iron, soldering station, LBPSU
|Type=
|Type=Soldering
|Difficulty=
|Difficulty=3. Hard
}}
}}
==Problem description==
==Problem description==

Latest revision as of 10:25, 9 July 2024

Simatic PS 307 Not turning on at all repair
Device Simatic PS 307
Affects part(s) TVS 1.5KE200CA, fuse
Needs equipment multimeter, soldering iron, soldering station, LBPSU
Difficulty ◉◉◉◌ Hard
Type Soldering


Problem description

Repairing Siemens Simatic PS 307 industrial power supply that doesn't turn on when powered. This particular issue is associated with a blown fuse and a shorted TVS diode.

Shorted diode, 1.5KE200CA (Figure 1)

Symptoms

  • Not reacting to power when plugged in
  • No output voltage
  • No LED lights turning on

Solution

Diagnostic Steps

  • Disassemble the device
  • Measure with a multimeter the legs of the full bridge rectifier, if you have short on + and - then you have a different issue, if you measure a short on either +- and the ~~ pins, then you also have a different problem, the rectifier might be shorted
  • For this issue, you should measure a short between both ~~ pins on the rectifier and a blown fuse
  • If that's the case, inject voltage into the pins and check what gets hot
  • In this case, it was the diode in figure 1

Repair Steps

Desolder the diode and check if the short is gone, if so, replace it along with the fuse with new ones and test if that fixes it. In this case, that was all it and after replacement the power supply started working again.